The instructions contained in this manual are not intended to cover all of the details or
variations in equipment, or to provide for every possible contingency concerning
installation, operation, or maintenance. Should further information be required or if
problems arise which are not covered sufficiently, contact your local Toshiba sales
office or (800) 231-1412 or by e-mail at toshibaups@tic.toshiba.com.
The contents of this instruction manual shall not become a part of or modify any prior or
existing agreement, commitment, or relationship. The sales contract contains the entire
obligation of Toshiba International Corporation (TIC) 's Uninterruptible Power Systems
(UPS) Division. The warranty contained in the contract between the parties is the sole
warranty of TIC's UPS Division and any statements contained herein do not create new
warranties or modify the existing warranty.
Any electrical or mechanical modifications to this equipment without prior
written consent of Toshiba International Corporation will void all warranties and
may void the UL/CUL listing. Unauthorized modifications can also result in
personal injury, death, or destruction of the equipment.

Complete the information below for the UPS received.
Unless otherwise specified on the warranty card, the warranty period for the UPS or
UPS part is 36 months from the shipment date (see TIC Bill of Lading).
Unless otherwise specified on the warranty card, the warranty period for a UPS battery
is 24 months from the shipment date (see TIC Bill of Lading).
Please complete the following information and retain for your records.
January, 2007





The purpose of this manual is to provide information on how to safely install, operate,
and maintain your TIC power electronics product. This manual includes a section of
general safety instructions that describes the warning labels and symbols that are used
throughout the manual. Read the manual completely before installing, operating, or
performing maintenance on this equipment.
The scope of this manual is to describe the requirements for an On-Line Uninterruptible
Power System (UPS). The UPS will supply a computer grade AC output sine wave
which is unaffected by the quality of the AC input. The input voltage is single phase and
the output voltage is single phase.
This manual and the accompanying drawings should be considered a permanent part of
the equipment and should be readily available for reference and review. Dimensions
shown in the manual are in metric and/or the English equivalent.
TIC reserves the right, without prior notice, to update information, make product
changes, or to discontinue any product or service identified in this publication.

TOSHIBA is a registered trademark of Toshiba Corporation. All other product or trade
references appearing in this manual are registered trademarks of their respective
owners.
Toshiba International Corporation (TIC) shall not be liable for direct, indirect,
special, or consequential damages resulting from the use of the information
contained within this manual.
This manual is copyrighted. No part of this manual may be photocopied or reproduced
in any form without the prior written consent of Toshiba International Corporation.
© Copyright 2006 Toshiba International Corporation.
All rights reserved.
Printed in the U.S.A.

Toshiba International Corporation’s Customer Support Center can be contacted to
obtain help in resolving any Uninterruptible Power System problems that you may
experience or to provide application information.
The center is open from 8 a.m. to 5 p.m. (CST), Monday through Friday. The Support
Center’s toll free number is US (800) 231-1412, Fax (713) 896-5212.
The email address is toshibaups@tic.toshiba.com.
You may also contact Toshiba International Corporation by writing to:
13131 West Little York Road
Attn: 1000 Series UPS Product Manager.
For further information on Toshiba International Corporation’s products and services,
please visit our website at www.toshiba.com/ind
Toshiba International Corporation · Houston, Texas 77041-9990

complies with the conditions of a Class B digital device. The product has been
established as offering sufficient protection against dangerous interference for
installations in a residential area. Installation and use of the equipment should comply
with the instructions provided in order to avoid interference due to the amount of radio
frequency energy that is radiated and generated by the equipment.
TIC cannot assure that no interference will occur. Turn the unit on and off to help
determine if the radio or television reception is found to be influenced by harmful
interference from the equipment. If required, use one of the following measures to
minimize the negative effects of interference:
assistance.
This Class B Interference Causing Equipment meets all requirements of the Canadian
Interference Causing Equipment Regulations ICES–003. Cet appareil numérique de la
classe B respecte toutes les exigences du Reglement sur le matériel brouilleur du
Canada.
FCC Part 15

Declaration of Conformity Request
Units labeled with a CE mark comply with the following standards and directives:
Harmonic Standards: EN 50091-1-1 and EN 50091-2.
certain voltage limits.
93/68/EEC, Amending Directive 73/23/EEC.
89/336/EEC, Council Directive relating to electromagnetic compatibility.
92/31/EEC, Amending Directive 89/336/EEC relating to EMC.
The EC Declaration of Conformity is available upon request for products with a CE
mark.

DO NOT attempt to install, operate, maintain or dispose of this equipment until you
have read and understood all of the product safety information and directions that are
contained in this instruction manual.
Safety Alert Symbol / Signal Words
The Safety Alert Symbol indicates that a potential personal injury hazard exists. The
symbol is comprised of an equilateral triangle enclosing an exclamation mark.
Listed below are the signal words that are used throughout this manual followed by their
descriptions and associated symbols. When the words DANGER, WARNING, and
information that must be carefully adhered to.
symbol indicates that an imminently hazardous situation exists that, if not avoided,
will result in death or serious injury to personnel.

symbol indicates that a potentially hazardous situation exists that, if not avoided,
could result in death or serious injury to personnel.
preceded by the safety alert symbol indicates that a potentially hazardous situation
exists that, if not avoided, may result in minor or moderate injury.
hazardous situation exists which, if not avoided, may result in equipment and
property damage.

Other warning symbols may appear in conjunction with the Danger, Warning, and
particular areas where special care and/or procedures are required in order to prevent
serious injury and possible death.
from an electrical shock or burn. The symbol is comprised of an equilateral triangle
enclosing a lightning bolt.
from exploding parts. It is comprised of an equilateral triangle enclosing an
explosion image.
Special Symbols

This manual contains important instructions that should be followed during the
installation, maintenance, and operation of the UPS and its batteries to assure safe and
proper operation.
to the equipment or when performing maintenance.
nor do they have an output disconnect for the ac output. Therefore, a user-installed
circuit breaker should be provided between the UPS output and the load input.
Qualified Personnel is one that has the skills and knowledge relating to the
construction, installation, operation, and maintenance of the electrical equipment and
has received safety training on the hazards involved (Refer to the latest edition of NFPA
70E for additional safety requirements).
Qualified Personnel shall:
circuits and equipment, and clear faults in accordance with established safety
practices.
rubber gloves, hard hats, safety glasses, face shields, flash clothing, etc., in
accordance with established safety practices.
precautions.
Qualified Personnel ONLY!

For further information on workplace safety visit www.osha.gov
Misuse of this equipment could result in injury and equipment damage. In no event will
Toshiba Corporation be responsible or liable for either indirect or consequential damage
or injury that may result from the misuse of this equipment.
Do not dispose of the batteries in a fire. The batteries may explode.
Do not open or mutilate the batteries. Released electrolyte is harmful to the eyes and
skin and could also be toxic.
A battery can present a risk of electrical shock and high short circuit current.

—Strict adherence to the following precautions is a requirement when working with
To be performed by Qualified Personnel only.
source.
remove source of ground.
Contact with any part of a grounded battery can result in electrical shock.
The likelihood of shock will be reduced if such grounds are removed prior to
installation or maintenance.
batteries—

LA SÉCURITÉ CONSERVER CES INSTRUCTIONS
Cette notice contient des instructions importantes concernant la sécurité.
Une battery peut présenter un risque de choc électrique, de brûlure par transfert d'
énergie.
L' élimination des batteries est règlementèe. Consulter les codes locaux à cet effet.

CAUTION
Upon receipt of the UPS, an inspection for shipping damage should be performed. Use
attached to packing material.
Check the unit for loose, broken, bent or otherwise damaged parts. If damage has
occurred during shipping, keep all original crating and packing materials for return to
the shipping agent. The warranty does not apply to damage incurred during shipping.
Ensure that the rated capacity and the model number specified on the nameplate
conform to the order specifications.
During periods of non-use, the following guidelines are recommended for storage.
the batteries.
wood or metal pallet.
will require recharging more frequently during storage.
Avoid the following storage locations:

every 9 months.
batteries every 6 months. • If stored at an ambient temperature of 30° – 40° C (86° – 104° F), recharge the batteries every 3 months.
Please contact your local or state environmental agency for details on disposal of
electrical components and packaging in your particular area.
It is illegal to dump lead-acid batteries in landfills or dispose of improperly.
Please help our Earth by contacting the environmental protection agencies in your area,
the battery manufacturer, or call Toshiba toll-free at (800) 231-1412 for more
information about recycling.
Storage Maintenance · Disposal

CAUTION
sides for air ventilation and for maintenance.
vibration.
metal particles, or flammable gases.
earth ground will reduce the effects of electrical noise and will reduce the potential
for electrical shock.
inside the UPS.
Although RFI noise filters are installed inside of the unit, there is no guarantee that
the UPS will not influence some sensitive devices that are operating near by. If such
interference is experienced, the UPS should be installed farther away from the
affected equipment and/or powered from a different source than that of the affected
equipment.
established lockout/tagout procedures, connect the power source wiring of the
correct voltage to the input terminals of the UPS.

Wiring Methods and Article 310 – Conductors For General Wiring). Size the
branch circuit conductors in accordance with NEC Table 310.16.
Conductor Routing and Grounding
circuits.
reduce electrical noise.
output power, and control circuits.
THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND.

CAUTION
the rated input voltage. The input frequency must be within the rated input
frequency range. Voltages and frequencies outside of the permissible range may
activate the internal protection devices.
rated output of the UPS.
with motors that require a long starting time, such as vacuum cleaners and machine
tools (over sizing the UPS for lock rotor current would be required).
UPS.
UPS off. The required discharge time for each UPS typeform is provided via a
cabinet label and a CHARGE LED. Wait for at least the minimum time indicated on
the label and ensure that the CHARGE LED has gone out before opening the door
of the UPS once the UPS power has been turned off.
representative for repair information.
immediately.

the unit to cool before coming in contact with these items.
being powered by the UPS.
location as deemed required by Qualified Personnel.
While operating in the inverter mode, placing the breaker in the OFF position will
switch the UPS to the battery backup mode. The output of the UPS will continue
uninterrupted to the load. The unit must be in the bypass mode at the time that the
breaker is placed in the OFF position for the UPS to shutdown power to the load. After an Emergency Power Off (EPO), do not reset the breaker until the UPS has been
fully discharged. The UPS could be damaged if the unit is not fully discharged before
the breaker is reset.

The information provided in this manual covers single phase 1000 – 3000 VA
uninterruptible power systems (UPS). Included in this manual is information on the
installation, operation, safety precautions, shipping, and storage of the equipment.
Installation must be carried out in accordance with this manual. Electrical installations
must also follow local legislation and regulations. Only qualified personnel should
install this equipment. Failure to comply with the warnings and precautions could prove
to be fatal. 2. System Description
The purpose of the UPS is to protect sensitive systems from poor quality utility power,
complete loss of power, or other associated problems. System types include computers,
workstations, process control systems, telecommunications systems, sales terminals, or
other critical instrumentation.
Electrical interference may occur causing problems in AC power. Interference may
come from lightning, the power company, radio transmissions, or motors. Normal
operation of sensitive electrical equipment requires protection against power outages,
low or high voltage levels, frequency variations, differential and common-mode noises,
and transients.
In order to prevent power line problems from reaching critical systems and causing
damage to software, hardware or causing equipment to malfunction, the UPS helps by
maintaining a constant voltage, isolating critical load output, and cleaning the utility AC
power.

2.1 General Description
As a double conversion on-line UPS, it is able to supply uninterrupted, clean
single-phase power to your critical systems while keeping batteries charged
continuously, even if the utility power fails.
Other features of the UPS includes
In the event that a power failure lasts longer than the UPS backup time, the UPS will
shut down. Upon power restoration, the UPS will restart automatically, which includes
output power being restored to the load and the start of battery recharge.
See following Figure 1 for systemic applicable of the UPS system.



Figure 1. Block diagram
rectifier feeding power to the inverter and battery converter.
2.2 Efficiency Optimizer Function
The Efficiency Optimizer function is a new feature for the UPS that increases the cost
effectiveness of the UPS by minimizing power losses and reduces power consumption.
IGBT Control · SNMP Port/Dry Contact · IGBT Control

Alternating between bypass and on-line modes is achieved automatically and in
accordance with the conditions of the utility power. On-line mode may be used during
times of utility power irregularities. The bypass mode should be used when power flows
smoothly in order to obtain the greatest efficiency. Irregularities can be detected in less
than a second and the on-line mode can be reactivated immediately. Switching back to
online mode occurs when the input voltage exceeds ±10% (or ±15% selectable), when
the input frequency exceeds ±3Hz, or when no input line is available.
Although high efficiency is standard, the default operation is the on-line mode. From
the LCD display panel, Bypass can be activated as required or On-line operation can be
run permanently if preferred.
2.3 Free Run Mode
Free run mode is a mode of operation in which the output frequency does not match
input frequency. The UPS operates in free run mode when the input frequency is outside
of the selected input frequency range. When starting the UPS, the targeted frequency is
50 or 60 Hz ±0.25Hz. Refer to Section 4.3 to set up bypass availability while running in
free run mode.
2.4 Diagnostic Tests
When the UPS is started, a diagnostic test is executed automatically that checks the
electronics and battery, and reports any problems on the LCD display.
The advanced battery management system monitors the performance of the battery and
will indicate if battery replacement is required. The battery management system tests
the battery every 30 days of normal mode operation. A battery discharge test is
performed and reports any problems on the LCD display.
Except during the first 24 hours after startup while the UPS is in charging mode,
diagnostic tests can be performed manually from the front panel when required.
2.5 System Configuration
The UPS device and the internal backup battery make up the system. Depending on the
site and load requirements of the installation, available options may be utilized to create
a tailored solution.

Planning a UPS system should include the following considerations:
Allow a margin for future expansion or calculation inaccuracies from measuring
power requirements.
the UPS nominal power rating then the actual backup time will be longer.
The following UPS models are available.
Model Backup time Internal
Recharge time to 90%
UPS 1000VA 7 min 4 hours
UPS 1500VA 6 min 4 hours
UPS 2000VA 7 min 4 hours
UPS 3000VA 6 min 4 hours
Additional External Battery Cabinets are available if more back-up time is needed.
batteries · capacity

Please adhere to the following instructions if the UPS is not installed when received:
air.
In order to maintain the vitality of the batteries, ensure that the UPS is recharged every 6
months for at least 8 hours during storage.

4.1 Environment
To ensure safe and proper operation, ensure that the installation conforms to the
following specifications.
Ensure that the installation location is consistent with the following:
a recommended temperature range of 15° C to 25° C.
inch) behind and 50mm (2 inch) on the sides of the UPS for ventilation.
The External Battery Cabinets must be installed next to or underneath the UPS.

4.2 Rear Panel Views
1000VA – 1500VA Tower Rear Panel

2000VA – 3000VA Tower Rear Panel


1000 – 1500 VA Rack mount (2U) Rear Panel

2000 – 3000 VA Rack mount (2U) Rear Panel

4.3 Connection to main supply and loads (1000 – 3000 VA)
The input cable is supplied with all models.
connecting the External Battery Cabinets.
External Battery Cabinet to the UPS. If more than one battery cabinet is required,
use the supplied cable.
pack quantity as when using the External Battery Cabinets.
The batteries will charge automatically when connected to the main supply.
The UPS may be used immediately to power a load. However, the maximum
battery back-up time will not be available until the recommended 8-hour minimum
charge time has completed.
that draws half-wave rectified current, such as hair dryers or vacuum cleaners.
connections are used.


Figure 2 Example of Installation of Plug & Play products.

4.4 Front Panel Settings
Listed below are the default settings of the primary UPS parameters.
Settings Options Default Remarks 1) O/P VOLT SET (output voltage set)
100V/110V/115V/120V/127V 208/220/230/240 Vac 120V 230V
120V (FOR LV series) 230V (FOR HV series)
+/- 2% +/- 5% +/- 7%
+/- 5% Input Frequency range in Free Run mode
+/- 10% +10% -15% +15% -20%
Input Voltage range when Bypass mode is on
If ON, enable UPS runs on Asynchronous mode. For example: If input freq 55Hz output freq stays at 60Hz. If OFF, disable UPS runs on synchronous mode. For example: If input freq 55Hz, UPS will go to battery mode. 5) HE MODE SET
ON
If ON, enable UPS runs in High efficiency mode. The unit will be in bypass mode with 95% or higher efficiency. If OFF, the unit will be in the online mode with 85% efficiency. 6) MANUAL BYPASS
OFF
ON/OFF OFF If ON, enable UPS switch to Bypass mode immediately.
+10% -15%

Settings Options Default Remarks 7) OUTLET SETTING
GROUP1/GROUP2 Option 1: 1 On /2 On Option 2: 1 Off /2 On Option 3: 1 Off /2 Off Option 4: 1 On /2 Off
This is a load-shed feature.
Perform battery test immediately
ON/OFF
OFF
10)BAT CABINET SET
Shown options when battery Cabinets are connected
Alarm on main computer connected at wrong polarity or Installation to main supply without group. 12) LANGUAGE ENGLISH GERMAN FRENCH SPANISH ITALIAN
DISABLE
ENGLISH
ENABLE/CHANGE ENABLE Option to enable and disable the RS232 port. USB share the communication line with RS232. Only one option may be used at a time.
Complete the installation entirely before changing the default settings or connecting a load to the
UPS.
Option 1

At the rear of the UPS is an interface that allows direct communication with a computer
system (see figure 2). There is a RS232 serial data interface, a USB data interface, and
an emergency power off switch. The RS232 port and the USB interface cannot be used
simultaneously.
In addition there is an optional interface slot that allows for the installation of
communications cards. It may be used in parallel with either the RS232 or USB ports.
An SNMP/WEB card is available for the optional interface slot that allows for the
RemotEye II to manage and monitor the system over a network or over the internet.
5.1 RS-232 Standard Interface Port
Only the communication cable provided with the UPS may be used to connect the UPS
to a computer when using the RS232 port of the UPS. Ensure that the operating system
of the computer supports RS232 communications. Other advanced power protection
solutions, such as SNMP, are available from your dealer.
The RS-232 interface uses a 9-pin D-sub connector. The names and functions of the port
pins are listed in the following table.

DB9 Female Connector Outline
Pin # Signal Direction (re UPS) Functions
2 TxD Output TxD Output
3 RxD Input RxD / Inverter Off Input
6 Output Ac Fail Output
8 Output Low Battery Output
9 Output 8–24 VDC Power
(facing connector) · 5 Common Common

5.2 Dry Contact Interface (optional card)
DB9 Male Connector Outline

Pin # Description I/O Type
1 UPS fail, relay contact, normally open, active close. output
2 Summary alarm, relay contact, normally open, active close.
One of the following signals activate this signal:
3 GND for secondary
4 Remote shutdown input
6 Bypass active, normally open, active close output
7 Battery low, normally open, active close output
8 Battery mode shutdown input
9 Utility fail, normally open, active close output
5.3 USB Port
Connecting the UPS to a computer using the USB port of the computer requires USB
compliant hardware, PC operating system support, and a UPS driver. The RS232 serial
(facing connector) · output · 5 Common

port cannot be used when using the USB port. The USB cable is a standard cable and
may be purchased separately.
5.4 EPO Port (emergency power off)
A customer-supplied switch located remotely may be used to open the EPO connection
and force the UPS output receptacles to be switched off. The EPO function shuts down
the equipment immediately. An EPO will not provide an orderly shutdown. The UPS
will have to be manually restarted in order to regain power to the outlets.
After an Emergency Power Off (EPO), do not reset the breaker until the UPS has been
fully discharged. The UPS could be damaged if the unit is not fully discharged before
the breaker is reset.
5.5 Network Transient Protector
The network transient protector, located on the back panel, has both IN and OUT RJ45
10 baseT jacks and will protect a single network connector. Connect the input connector
to the jack labeled IN, and the output connector to the jack labeled OUT.
5.6 Load Segments
The sets of receptacles known as load segments provide organized shutdown and
startup of the equipment. Less critical equipment can be turned off during power
outages saving battery power for critical loads. The load group status can be viewed
from the LCD display and can be changed if necessary.

Load 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
1000VA Backup (min) 150 56 38 30 23 19 15 12 10 7
1500VA Backup (min) 80 37 21 19 18 15 13 11 8 6
2000VA Backup (min) 150 68 38 26 19 14 11 9 8 7
3000VA Backup (min) 80 40 25 19 15 12 9 8 7 6

Normal ongoing UPS operation requires little or no user input. Startup and shutdown requirements of the user are discussed in this section.
6.1 UPS Startup and Shutdown
properly grounded outlet.
inverter startup. A successful completion allows for output power via the outlets.
up when output power has started and the LCD display will show Line Mode.
Shutting Down the UPS
the UPS will shut down.
6.2 Button Operation
(a) Press and hold the Load ON/OFF button for at least 3 seconds to turn on the UPS.
(b) While the UPS is operating, press and hold the Load ON/OFF button for at least 3 seconds to turn off the UPS.
Starting the UPS

” is the Enter button.
(a) Press and hold the Enter button for at least 2 seconds to read the parameter settings of the UPS. Press the Enter button again to read the next parameter.
(b) Ten seconds of inactivity will return the display to the original status.
(a) Press and hold the Function button for at least 2 seconds to access the selectable
parameters. Press the Function button again to view the next parameter.
(b) Press the Enter button to view or change the displayed parameter.
(c) Ten seconds of inactivity will return the display to the original status.
6.3 Control Panel Functions The front panel is composed of five LED indicators, an LCD screen, and a speaker for audible alarms.
ON/ — is on when the UPS is turned on (green).
ON-LINE/ — is on when in the Normal or Static Bypass modes. Also indicates
that there is voltage at the output terminals (green).
ON-BAT/ — is on while operating in the Battery mode.
BYPASS/ — is on while operating in the Bypass mode (yellow).
ALARM/ — is on during active UPS internal errors (red). FAULT is accompanied by an audible alarm. Press any of the front panel buttons to cancel the alarm.

Status of the UPS, measurements, and alarms are all indicated on the LCD screen.
Rack Unit Tower Unit
Figure 3 Control panel
6.4 Normal Display
The UPS status is shown in the normal display mode. The UPS Meters display and the
Setting display may be accessed by pressing the Return button on Tower Unit and
FUNC button on the Rack Unit.
6.5 UPS Meters Display
Listed below are the parameters available for viewing from the UPS meters display.
Press this button to scroll through the parameters.
O/P VOLT= xxx.xV Shows Output AC Voltage
O/P FREQ= xx.x Hz Shows Output Frequency
I/P VOL T= xxx.xV Shows Input AC Voltage
I/P FREQ= xx.x Hz Shows Input Frequency
BAT VOLT= xx.xV Shows Battery Voltage
O/P LOAD%= xx% Shows Load % of Max Load
O/P W= xW Shows Output Watts
O/P VA= xVA Shows Output VA
O/P CURR= xA Shows Output Current
LCD Message Description

BACKUP TIME= xx min Shows Estimated Backup Time in Minutes
BAT CHARG= xx% Shows Approximate Percentage of Battery Capacity
TEMPERATURE= xxC Shows Approximate Ambient Temperature
BAT PACK NUM= x Shows External Battery Pack Number
RATING = xxxxVA Shows UPS Rating
CPU VERSION xx.x Shows CPU Version
6.6 UPS Configurations
The first configuration parameter will be shown on the LCD display.
Press the Enter button to select the setting.
the selection. See the table on page 12 for a complete listing of the user-settable
parameters.
and return to normal mode displaying Line mode.

6.7 UPS Manual Test
Manual UPS and Battery tests may be performed from the UPS configuration screen.
Tests may be performed when the battery is not being charged.
To run the battery test scroll to the “Manual Bat Test” parameter press the Enter button
twice.
to OFF because the load will not be protected by the unit when Manual Bypass is ON.
*** Note: Turn off the UPS and keep the AC power on to use the Generator function.
(go to normal mode for \Generator\OFF).
6.8 Interpreting UPS Messages
Troubleshooting procedures described here provide instructions to be used to isolate
UPS malfunctions.
Start the troubleshooting procedure in the event of a control panel alarm.
6.9 Audible Alarms
5-second intervals.
flashing) the UPS will beep twice at 5-second intervals.
will provide a constant audible alarm and display an error message on the LCD
display.
6.10 Silencing an Alarm
With the exception of a LOW BATTERY Alarm, pressing any of the front panel buttons
will turn off the alarm. Select Silent Alarm Mode to disable all audible alarms.

6.11 Troubleshooting
Displayed on LCD Audible Alarm Alarm Description What You Should Do Output Overload Two Beeps/sec The UPS is overloaded (in
Remove loads from the UPS; least to most critical. If this solves the problem, the UPS will return to normal operation.
Line Mode). More power required than the UPS can provide. The UPS operates in bypass.
Battery Test No Beeps Battery test active. No action needed.
User Notification only.
Over-Charge Constant Beep Overcharged Batteries. Turn off loads. Turn off UPS. Call service @ 1-877-867-8773 Low Battery 2 Beeps/5 sec UPS operating on Battery Power and will shut down soon due to low battery voltage.
The unit will restart Automatically when acceptable power returns.
On-Battery 1 Beep/5 sec UPS operating on Battery Power.
Save your data and perform a controlled shutdown. Charger Failure Constant Beep Failed Charger. Call service @ 1-877-867-8773
Over-Temperature Constant Beep High ambient
Ensure that the UPS fans and vents are not blocked, and that the ambient temp. is < 40° C. If problem persists call service @ 1-877-867-8773 Output Short Constant Beep Output short circuit. Call service @ 1-877-867-8773 High output Voltage Constant Beep High output voltage. Call service @ 1-877-867-8773 Low Output Voltage Constant Beep Low output voltage. Call service @ 1-877-867-8773
Temperature.
Bus Fault 2 Beeps/sec High internal DC bus Voltage.
Turn off loads. Turn off UPS. Call service @ 1-877-867-8773 Site Wiring Fault 1 Beep/sec Voltage detected between neutral and ground.
UPS main connector wrong polarity. Rotate the connector (Schuko-electric contact). UPS installed to main supply without ground. See section 4.4 for information on how to disable the Site wiring alarm.
Line Abnormal 1 Beep/sec Wrong AC Line backed up during auto restart.

With a minimal amount of maintenance you can expect years of satisfactory operation
from the UPS unit. The most critical issues for the reliability of the UPS are
environmental issues. Ensure that the temperature and humidity are always in
accordance with the specifications and keep the area around the unit clean and dust free.
The typical battery lifetime is 4 years when operated at 25° C.
Check the back-up time capability of the UPS/battery at 6 to 12 month intervals to
ensure adequate support for the application.

8.1 Power Range 1000-3000 VA (120V)
Tower US 120V Model
UT1A1A010C6R KB2
UT1A1A015C6R KB2
UT1A1A020C6R KB2
UT1A1A030C6R KB2
Input Voltage 120 VAC (80 – 144 V) Voltage Range +20% to -33% Capacity (VA) 1000 VA 1500 VA 2000 VA 3000 VA Capacity (W) 700 W 1050 W 1400 W 2100 W Frequency 50 / 60 Hz auto sensing Power Factor Greater than 0.97 Topology True on-line Double conversion Input PF correction Output Voltage 120 VAC Frequency 50 / 60 Hz auto sensing Wave Form Sine wave, zero transfer time Load Power Factor
Rated Current 8.3 A 12.5 A 16.6 A 25 A Overload Capacity
125% for 1 min 150% for 10 sec
Crest Factor 3.0 at full load Battery DC Voltage (Tower & 2U)
36 V / 12 V 9 AH x 3 72V / 12 V 7.2AH x 6 72V / 12 V 9AH x 6 Backup Time (Tower & 2U)
6 min (full load) Interface RS-232 and USB standard RemotEye II® and EMD option Physical Dimensions (Tower)
7 min (full load)
6 min (full load)
7 min (full load)
16.5”L x 6.0”W x 9.4”H 16.7"L x 8.9"W x 14.2"H
16.7”L x 16.9”W x 3.5”H 25.0"L x 16.9"W x 3.5"H
35.6 lbs / 37.6 lbs 37.4 lbs / 37.6 lbs 68.4 lbs / 69.5 lbs 72.6 lbs / 71.5 lbs
Line Cord 5-15P 5-20P L5-30P Receptacles (Tower/2U)
NEMA 5 - 15 P (6 / 6) NEMA 5-15 P (12 / 4)
Altitude 11500 ft (3500 m) above sea level Warranty Three years on electronics Two years full replacement on battery (See Toshiba warranty policy for full details.)

8.2 Power Range 1000-3000 VA (230V)
Tower International 230V Model UT1E1E010C6 UT1E1E015C6 UT1E1E020C6 UT1E1E030C6
International 230V Model UT1E1E010C6R KB2
UT1E1E020C6R KB2
UT1E1E030C6R KB2
230 VAC (161 – 276 V)
Capacity (VA) 1000 VA 1500 VA 2000 VA 3000 VA Capacity (W) 700 W 1050 W 1400 W 2100 W Frequency 50 / 60 Hz auto sensing Power Factor Greater than 0.97 Topology True on-line, Double conversion Input PF correction Output Voltage (International)
Frequency 50 / 60 Hz auto sensing Wave Form Sine wave, zero transfer time Load Power Factor
125% for 1 min., 150% for 10 sec.
Crest Factor 3.0 at full load Battery DC Voltage (Tower & 2U)
36 V / 12 V 9 AH x 3 72V / 12 V 7.2AH x 6 72V / 12 V 9AH x 6 Backup Time (Tower & 2U)
6 min (full load) Interface RS-232 and USB standard RemotEye II® and EMD option Physical Dimensions (Tower)
7 min (full load)
6 min (full load)
7 min (full load)
16.5”L x 6.0”W x 9.4”H 16.7" L x 8.9" W x 14.2" H
16.7”L x 16.9”W x 3.5”H "25.0""L x 16.9""W x 3.5""H"
35.6 lbs / 37.6 lbs 37.4 lbs / 37.6 lbs 68.4 lbs / 69.5 lbs 72.6 lbs / 71.5 lbs
IEC 320 (4 / 4) IEC 320 (8 / 8)
Altitude 11500 ft (3500 m) above sea level Warranty Three years on electronics Two years full replacement on battery (See Toshiba warranty policy for full details.)

TOSHIBA INTERNATIONAL CORPORATION
LIMITED WARRANTY POLICY
(48 contiguous U.S. States, Canada & Mexico)
TOSHIBA INTERNATIONAL CORPORATION (“TIC”) warrants that any Uninterruptible Power System (“UPS”) and Uninterruptible Power System Battery (“BATTERY”) (internal UPS battery and/or external battery cabinet) sold by TIC to an end user (“User”) shall be free of defects in material and workmanship. This warranty applies to all UPS series in table below:
UPS Unit Battery UPS Series Unit kVA UPS Warranty (1)
1000 1.0, 1.5, 2, 3 36 months from shipment
24 months from shipment
No, Depot Depot Only
Note (1) Shipment date is determined by date on the TIC Bill of Lading. Note (2) For 1000 Series UPS the warranty applies if the units are sent and returned (paid for) by the user to/from the Toshiba Plant or a Toshiba designated Authorized Service Center. Note (3) Shipment date is determined by date on the TIC Bill of Lading * 24 month full replacement, 36 month pro-rated warranty (5 yr total) Note (4) For 1000 Series UPS the warranty applies if the units are sent and returned (paid for) by the user to/from the Toshiba Plant or a Toshiba Designated Authorized Service Center. Note (5) Toshiba Service dispatch available at normal business hours. Contacting Toshiba is possible 24 hours 7 days a week. User can purchase 24x7 dispatch programs offered through TIC’s Service Department. TIC also encourages users to review TIC’s UPS Preventative and Scheduled Maintenance/Parts Programs for Premium coverage. If any UPS, UPS parts, and/or BATTERY fail to conform or is defective then TIC, at its option, will repair or replace it at the premises of the User (On-Site), The warranty period for a UPS or a UPS part is 12-36 months from shipment except for cases stated in table above. The warranty period for the BATTERY is 24 months from shipment except for cases stated in the table above.

Valve Regulated Lead Acid (VRLA) Batteries for Toshiba UPS Required Operating, Installation, and
*** > 9AHr Typically extended runtimes < 9AHr Typically Single Phase Systems.

Credit for Replacement Battery When Approved Warranty Time from Shipments UPS Batteries Cost to Customer Months % Credit % List Price 0-24 100 0 25-30 55 45 31-36 45 55 37-42 35 65 43-48 25 75 49-54 15 85 55-60 5 95
Maintenance Conditions

2. This Warranty does not cover damage or defect caused by misuse, improper application, wrong or inadequate electrical current/voltage/frequency, inadequate connections, inadequate water or drain services, user negligence, repair by non-Toshiba designated personnel, accident during shipment, tampering, alterations, a change in UPS and/or BATTERY location or application, exposure to the elements, acts of God, force nature, theft, sabotage, installation contrary to TIC's recommendations or specifications (Published Operation Manuals), also if serial numbers have been altered, defaced, or removed. 3. Repair or replacement of a defective UPS, UPS part, and/or BATTERY does not extend the respective original warranty period. All defective UPS, UPS parts, and/or BATTERIES shall be the property of TIC upon replacement. 4. This warranty shall constitute the sole and exclusive remedy of all purchasers and users of the UPS, UPS part, and/or BATTERY. TIC’s responsibility for UPS, UPS Parts, and/or BATTERY shall not exceed one times the net UPS and/or BATTERY purchase price. TIC HEREBY EXPRESSLY DISCLAIMS ALL OTHER EXPRESS, STATUTORY AND IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
PROCEDURE User must contact TIC via e-mail upsservice@tic.toshiba.com, or phone 1-800-231-1412, no later than 90 days after User’s discovery of occurrence or defect in UPS, UPS part, and/or BATTERY but in no event after the expiration of the respective warranty period. Subject to the limitations of this policy and product type, TIC service or TIC service representative shall repair/replace the UPS/part warranted hereunder, without charge for material, labor (on-site except in cases presented herein). If TIC determines that the requested repair is not covered under this limited warranty policy, then TIC shall advise customer and quote cost of repair. Repair charges shall be based on service parts price and prevailing service charges at the time of repair. If the case in process is a BATTERY (stand-alone and/or cabinet) TIC will use its published Battery Diagnostic Document to evaluate warranty applicability. First, TIC will make sure that the storage, maintenance, installation, and operating conditions were met; then the BATTERY capacity will be tested in accordance with the “performance test” guidelines IEEE STD 450. If the BATTERY fails to deliver 70% of its rated capacity it shall be deemed defective and be replaced. Either float or cyclic service will be used to determine the warranty credit (as per published Battery Diagnostic Document). The typical credit applied will be as in the table above.
MODIFICATIONS No representative, salesperson, agent, distributor, or employee of TIC is authorized to modify any of the terms of this warranty, unless modifications are made in writing and signed by an authorized TIC officer.

THIS WARRANTY REPRESENTS THE ENTIRE AGREEMENT BETWEEN TIC AND USER WITH RESPECT TO THE SUBJECT MATTER HEREIN AND SUPERSEDES ALL PRIOR OR CONTEMPORANEOUS ORAL OR WRITTEN COMMUNICATIONS, REPRESENTATIONS, UNDERSTANDINGS OR AGREEMENTS RELATING TO THIS SUBJECT.
End User:
Model Number:
Serial Number: