UNINTERRUPTIBLE POWER SYSTEMS

Toshiba Power Supply — UNINTERRUPTIBLE POWER SYSTEMS diagram (page 1)
Fig. 1
Toshiba Power Supply — UNINTERRUPTIBLE POWER SYSTEMS diagram (page 1)
Fig. 2

Isolated-Redundant

UPS Systems

Toshiba Power Supply — Isolated-Redundant diagram (page 1)
Fig. 3 · Isolated-Redundant

ß Mix and Match Modular kVA Sizes

Toshiba Power Supply — Isolated-Redundant diagram (page 1)
Fig. 4 · Isolated-Redundant

ß Mix and Match New and Existing Modules

ß Modules Can be in Separate Rooms

ß Simple Maintenance Scheme without Transfers to Utility Power

ß Sequential Installation and Startup

ß Extended Battery Backup Time in Blackouts

ß Higher Operating Efficiencies and Reliability

Toshiba Power Supply — Isolated-Redundant diagram (page 1)
Fig. 5 · Isolated-Redundant
Page 2 of the Toshiba Power Supply user manual — *UPSISOREDUNDNT060301*
Page 2 · click to enlarge
Page 2

ISOLATED-REDUNDANT UPS SYSTEMS

Toshiba Power Supply — ISOLATED-REDUNDANT UPS SYSTEMS diagram (page 2)
Fig. 6

Toshiba’s Isolated Redundant UPS System offers the ultimate in reliability, maintainability and availability. This UPS system delivers maximum design flexibility that is unmatched by any other configured UPS design.

Toshiba Power Supply — ISOLATED-REDUNDANT UPS SYSTEMS diagram (page 2)
Fig. 7

An isolated-redundant UPS system allows the user to never have critical loads exposed or fed from the utility source, even during UPS module failures or UPS module maintenance. The principal behind this system is that the critical load is divided into separated, isolated segments, which means that the failure of one segment cannot affect the other load segments. Reliability is maximized and common- mode failure is minimized!

Oversized Redundant UPS Module

Toshiba Power Supply — ISOLATED-REDUNDANT UPS SYSTEMS diagram (page 2)
Fig. 8

Each load segment can be a single, modular UPS system. If a UPS load segment failure causes a transfer to static bypass, the static bypass source is another standby UPS system.

In isolated redundant systems, the standby UPS system is always ready to support the critical load since it is on-line and keeps its own battery plant charged. A key requirement of this system is that the standby UPS system must accept a 100% step load with minimal transient voltage. Toshiba’s design can handle 100% step load without using the batteries and maintaining a less than 5% voltage distortion, making this UPS configuration the right choice for many customers.

UPS ADJUSTABLE SPEED DRIVES MOTORS CONTROLS INSTRUMENTATION PLC

Available Through:

INDUSTRIAL DIVISION

13131 West Little York Road, Houston, Texas 77041 Tel (713)466-0277 Fax (713)892-5212 US (800)231-1412 Canada (800)872-2192 Mexico 01(800)527-1204 www.toshiba.com/ind Copyright 3/2006

*UPSISOREDUNDNT060301*

Isolated-Redundant UPS Module

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Toshiba Power Supply

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Toshiba Power Supply

Be the first to ask — other owners or our team will answer.

Original document

Toshiba Power Supply manual PDF

2 pages·242 KB·Power Supply·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…