1F83-277 Heating & Air Conditioning Non-programmable, Auto Changeover, Multi-Stage/Heat

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use! Operator: Save these instructions for future use! Operator: Save these instructions for future use! Operator: Save these instructions for future use! Operator: Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. INJURY AND/OR PROPERTY DAMAGE. INJURY AND/OR PROPERTY DAMAGE. INJURY AND/OR PROPERTY DAMAGE. INJURY AND/OR PROPERTY DAMAGE.

PREPARATIONS

cription t Pump (No Aux. or Emergency Heat)Yes t Pump (with Aux. or Emergency Heat)Yes ndard Heat & Cooling SystemsYes Stage Heat & Two Stage CoolYes ndard Heat Only SystemsYes volt Heat Only Systems – Floor or Wall FurnacesYes ndard Central Air ConditioningYes or Oil HeatYes ctric FurnaceYes ronic (Hot Water) Zone Heat – 2 WiresYes ronic (Hot Water) Zone Heat – 3 WiresNo

FLAT BLADE SCREWDRIVER

WIRE CUTTER/STRIPPER

HAND OR POWER DRILL WITH 3/16 INCH DRILL BIT, IF NEEDED

SPIRIT LEVEL OR PLUMB BOB AND LINE OPTIONAL— THERMOSTAT DOES NOT NEED TO BE LEVEL TO WORK PROPERLY

REMOVING OLD THERMOSTAT REMOVING OLD THERMOSTAT REMOVING OLD THERMOSTAT REMOVING OLD THERMOSTAT REMOVING OLD THERMOSTAT

CAUTION !

To prevent electrical shock and/or equipment dam- To prevent electrical shock and/or equipment dam- To prevent electrical shock and/or equipment dam- To prevent electrical shock and/or equipment dam- To prevent electrical shock and/or equipment dam- age, disconnect electric power to system at main fuse age, disconnect electric power to system at main fuse age, disconnect electric power to system at main fuse age, disconnect electric power to system at main fuse age, disconnect electric power to system at main fuse or circuit breaker box until installation is complete. or circuit breaker box until installation is complete. or circuit breaker box until installation is complete. or circuit breaker box until installation is complete. or circuit breaker box until installation is complete.

Before removing wires from old thermostat's switching sub- base, label each wire label each wire label each wire label each wire label each wire with the terminal designation it was removed from.

Y2

1. Shut off electricity at the main fuse box until installation is complete. Ensure that electrical power is disconnected.

E/W1

R

Y1

O B L W2 G

2. Remove Old Thermostat Remove Old Thermostat Remove Old Thermostat Remove Old Thermostat Remove Old Thermostat: A standard heat/cool thermostat consists of three basic parts: a. The cover, which may be either a snap-on or

ELEC. GAS

AUTO ON

hinge type. b. The base, which is removed by loosening all

captive screws. c. The switching subbase, which is removed by

Figure 1 – Thermostat base Figure 1 – Thermostat base Figure 1 – Thermostat base Figure 1 – Thermostat base Figure 1 – Thermostat base

unscrewing the mounting screws that hold it on the wall or adaptor plate.

3. Remove the front cover of the old thermostat. With wires still attached still attached still attached still attached still attached, remove wall plate from the wall. If the old thermostat has a wall mounting plate, remove the thermostat and the wall mounting plate as an assembly.

Do not open mercury cells. If a cell becomes damaged, do not touch any spilled mercury. Wearing non-absorbent gloves, clean up the spilled mercury and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded.

4. Identify each wire attached to the old thermostat.
5. Disconnect the wires from the old thermostat one at a time. DO NOT LET WIRES FALL BACK INTO THE DO NOT LET WIRES FALL BACK INTO THE DO NOT LET WIRES FALL BACK INTO THE DO NOT LET WIRES FALL BACK INTO THE DO NOT LET WIRES FALL BACK INTO THE WALL.

Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container and return to White-Rodgers at 2895 Harrison Street, Batesville, AR 72501 for proper disposal.

6. Install new thermostat using the following procedures.

White-Rodgers is a division

of Emerson Electric Co.

PART NO. 37-6509A PART NO. 37-6509A PART NO. 37-6509A PART NO. 37-6509A PART NO. 37-6509A

www.white-rodgers.com

Mounting Hole · Mounting Hole · Elec-Gas Switch

Page 2 of the White Rodgers 1F83-277 user manual — NEUTRAL
Page 2 · click to enlarge
Page 2

MOUNTING AND WIRING MOUNTING AND WIRING MOUNTING AND WIRING MOUNTING AND WIRING MOUNTING AND WIRING

CAUTION !

WARNING !

Take care when securing and routing wires so they do Take care when securing and routing wires so they do Take care when securing and routing wires so they do Take care when securing and routing wires so they do Take care when securing and routing wires so they do not short to adjacent terminals or rear of thermostat. not short to adjacent terminals or rear of thermostat. not short to adjacent terminals or rear of thermostat. not short to adjacent terminals or rear of thermostat. not short to adjacent terminals or rear of thermostat. Personal injury and/or property damage may occur. Personal injury and/or property damage may occur. Personal injury and/or property damage may occur. Personal injury and/or property damage may occur. Personal injury and/or property damage may occur.

Do not use on circuits exceeding specified voltage. Do not use on circuits exceeding specified voltage. Do not use on circuits exceeding specified voltage. Do not use on circuits exceeding specified voltage. Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause Higher voltage will damage control and could cause Higher voltage will damage control and could cause Higher voltage will damage control and could cause Higher voltage will damage control and could cause shock or fire hazard. shock or fire hazard. shock or fire hazard. shock or fire hazard. shock or fire hazard.

Attach Thermostat Base to Wall Attach Thermostat Base to Wall Attach Thermostat Base to Wall Attach Thermostat Base to Wall Attach Thermostat Base to Wall

Do not short out terminals on gas valve or primary Do not short out terminals on gas valve or primary Do not short out terminals on gas valve or primary Do not short out terminals on gas valve or primary Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damage control to test. Short or incorrect wiring will damage control to test. Short or incorrect wiring will damage control to test. Short or incorrect wiring will damage control to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/or thermostat and could cause personal injury and/or thermostat and could cause personal injury and/or thermostat and could cause personal injury and/or thermostat and could cause personal injury and/or property damage. property damage. property damage. property damage. property damage.

1. Remove the packing material from the thermostat. Gently pull the cover straight off the base. Forcing or prying on the thermostat will cause damage to the unit.
2. Connect wires beneath terminal screws on base using appropriate wiring schematic (see figs. 2 through 4).

Thermostat installation and all components of the system shall conform to Class II circuits per the NEC code.

3. Place base over hole in wall and mark mounting hole locations on wall using base as a template.
4. Move base out of the way. Drill mounting holes.

Electric/Gas Switch (Fan Option) Electric/Gas Switch (Fan Option) Electric/Gas Switch (Fan Option) Electric/Gas Switch (Fan Option) Electric/Gas Switch (Fan Option)

The ELEC/GAS switch is factory set to the ELEC position. In this position, the thermostat will power the circulator fan on a call for heat. Electric heat systems require the switch to be in the ELEC position.

5. Fasten base loosely to wall, as shown in fig. 1, using two mounting screws. Place a level against bottom of base, adjust until level, and then tighten screws. (Leveling is for appearance only and will not affect thermostat operation.) If you are using existing mounting holes, or if holes drilled are too large and do not allow you to tighten base snugly, use plastic screw anchors to secure subbase.

If your system does not require that the thermostat power the circulator fan, this switch should be set to the GAS position. Typically, gas and oil heating systems do not require the thermostat to power the circulator fan during a call for heat. If your heat is gas or oil, the switch should be set to the GAS position.

6. Push excess wire into wall and plug hole with a fireresistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.

When the thermostat is configured for Heat Pump, the thermo- stat will always power the circulator fan on a call for heat in the HEAT mode. The ELEC/GAS switch must be set to match the type of Auxiliary heat your system uses for proper operation in the EMERgency mode.

Battery Location Battery Location Battery Location Battery Location Battery Location

2 "AA" alkaline batteries are included in the thermostat at the factory with a battery tag to prevent power drainage. You must remove the battery tag to engage the batteries.

If BATT is displayed, the batteries are low and should be replaced with fresh "AA" Energizer® alkaline batteries. To replace batteries, set system to OFF, install the batteries along the top of the base (see Fig. 1). The batteries must be installed with the positive (+) end to the left.

All wiring diagrams are for typical systems only. Refer to equipment manufacturers' instructions for specific system wir- ing information.

E/W1

THERMOSTAT

O

B

C Y1 Y2

SYSTEM G W2

L R

Reversing Valve Energized in Cool

Reversing Valve Energized in Heat,

SYSTEM MONITOR

Aux Relay (Stage 2)

SWITCH

or 1st Aux.

24 VAC 120 VAC

TRANSFORMER (Class II Current Limited)

Figure 2. Typical wiring diagram for single transformer heat pump systems

NOTE

If safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits.

E/W1

THERMOSTAT

O

B

C Y1 Y2

SYSTEM G W2

L R

CUT AND TAPE OFF!

SYSTEM MONITOR

HOT

SWITCH

or 1st Aux.

120 VAC 24 VAC

Aux Relay (Stage 2)

NEUTRAL

24 VAC 120 VAC

TWO COMMONS MUST BE JUMPERED TOGETHER!

TRANSFORMER (Class II Current Limited)

Figure 3. Typical wiring diagram for two transformer heat pump systems with NO safety circuits

Show 27 more labels / short text on this page
2nd Stage Compressor · Fan Relay · Emergency · Compressor · Mode · Off, Emergency · Contactor · Stage Relay · Mode · Hot · Neutral · Reversing · Reversing · 2nd Stage Compressor · Fan Relay Emergency · Limit or · Valve Energized in · Valve Energized in · Safety Switches · Heat, Off, Emergency · Compressor · Stage Relay · Cool Mode · Contactor · Hot · Mode · Neutral
Page 3 of the White Rodgers 1F83-277 user manual — 24 VAC 120 VAC
Page 3 · click to enlarge
Page 3

WIRING DIAGRAMS WIRING DIAGRAMS WIRING DIAGRAMS WIRING DIAGRAMS WIRING DIAGRAMS

NOTE

Polarity must be observed. If the HOT side of the second transformer is jumpered to the COMMON side of the first transformer a short will be made. Damage to equipment will occur when power is restored.

E/W1

THERMOSTAT

O

B

C Y1 Y2

G W2

L R

SYSTEM

HOT

24 VAC

120 VAC

or 1st Aux. Stage Relay

SYSTEM MONITOR

NEUTRAL

SWITCH

24 VAC ACCESSORY

NOTE

Aux Relay (Stage 2)

RELAY N.O.

The accessory relay scheme is required when safety circuits exist in both systems.

CONTACT

(Class II Current Limited)

COMMON

TWO COMMONS MUST BE JUMPERED TOGETHER!

HOT

COMMON

24 VAC 120 VAC

NEUTRAL

Heat Pump Transformer (Class II Current Limited)

Figure 4. Typical wiring diagram for two transformer heat pump systems with safety circuits in BOTH systems

Heat Pump Terminal Outputs Heat Pump Terminal Outputs Heat Pump Terminal Outputs Heat Pump Terminal Outputs Heat Pump Terminal Outputs

Refer to equipment manufacturers' instructions for specific system wiring information.

one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one trans- former, the two commons must be jumpered together.

You can configure the thermostat for use with the following heat pump system types: HEAT PUMP TYPE 1 HEAT PUMP TYPE 1 HEAT PUMP TYPE 1 HEAT PUMP TYPE 1 HEAT PUMP TYPE 1. Single stage compressor system; gas or electric backup.

Use the terminal output information below to help you wire the thermostat properly for your multi-stage system. After wiring, see CONFIGURATION section for proper thermostat configu- ration.

This thermostat is designed to operate a single-transformer system. If you have a two-transformer system, cut and tape off

THERMOSTAT TERMINALS (HEAT PUMP) SYSTEMLCRW2E/W1Y2Y1GOB Heat Pump 1Malfunction Light24 Volt (Common)24 Volt (Hot)Heat Mode 3rd stage Emergency mode 2nd stageHeat mode 2nd stage or Emergency Mode 1st stageNo OutputHeat and Cool mode 1st stage (compressor)Blower/Fan Energized on call for Heat and Cool Set GAS/ELEC switch for Emergency modeEnergized in Cool ModeEnergized in Heat OFF Emergency mode Heat Pump 22nd stage compressor

E/W1

THERMOSTAT

O

B

SYSTEM Y1

C R Y2

G

W2

Heat Relay Stage 1

24 VAC 120 VAC

Heat Mode Off Emergency

Heat Relay Stage 2

TRANSFORMER (Class II, Current Limited)

Figure 5. Typical wiring diagram for single transformer multi-stage systems

Show 35 more labels / short text on this page
Limit or · Limit or · Safety Switches · Safety Switches · Reversing · Emergency · Reversing · Valve Energized in · 2nd Stage Compressor · Fan Relay · Valve Energized in · Heat, Off, Emergency · Auxiliary · Heating Transformer · Cool Mode · Compressor · Mode · Contactor · Limit or · Limit or · Safety Switches · Safety Switches · Compressor · Contactor · Reversing · Stage 2 Reversing · Valve Energized in · Valve Energized in · Hot · Cool Mode · Compressor · Fan Relay · Neutral · Contactor · Stage 1
Page 4 of the White Rodgers 1F83-277 user manual — CAUTION !
Page 4 · click to enlarge
Page 4

Multi-Stage Terminal Outputs Multi-Stage Terminal Outputs Multi-Stage Terminal Outputs Multi-Stage Terminal Outputs Multi-Stage Terminal Outputs

Refer to equipment manufacturers' instructions for specific system wiring information.

one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one trans- former, the two commons must be jumpered together.

You can configure the thermostat for use with either multi-stage electric heat systems or multi-stage gas systems. When con- figured for electric heat, the G terminal (blower/fan) will be energized on a call for heat.

Use the terminal output information below to help you wire the thermostat properly for your multi-stage system. After wiring, see CONFIGURATION section for proper thermostat configu- ration.

This thermostat is designed to operate a single-transformer system. If you have a two-transformer system, cut and tape off

THERMOSTAT TERMINALS (MULTI-STAGE) SYSTEMLCRW2E/W1Y2Y1GOB Multi-stageMalfunction Light24 Volt (Common)24 Volt (Hot)Heat Mode 2nd stageHeat mode 1st stageCool Mode 2nd stageCool Mode 1st stageBlower/Fan Energized on call for Cool (and Heat if configured to Electric Heat)Energized in Cool ModeEnergized in Heat, Off, Emergency Modes

CHECK THERMOSTAT OPERATION CHECK THERMOSTAT OPERATION CHECK THERMOSTAT OPERATION CHECK THERMOSTAT OPERATION CHECK THERMOSTAT OPERATION

Emergency System Emergency System Emergency System Emergency System Emergency System

NOTE

EMER bypasses the Heat Pump to use the heat source wired to terminal E on the thermostat. EMER is typically used when compressor operation is not desired, or you prefer back-up heat only. 1. Press SYSTEM button to select EMER. EMER will flash on the display. 2. Press to adjust thermostat setting above room temperature. The Aux. heating system will begin to operate. The display will show STG1 flashing EMER

To prevent static discharge problems, touch side of To prevent static discharge problems, touch side of To prevent static discharge problems, touch side of To prevent static discharge problems, touch side of To prevent static discharge problems, touch side of thermostat to release static build-up before touching thermostat to release static build-up before touching thermostat to release static build-up before touching thermostat to release static build-up before touching thermostat to release static build-up before touching any keys. any keys. any keys. any keys. any keys.

If at any time during testing your system does not operate properly, contact a qualified serviceperson.

Fan Operation Fan Operation Fan Operation Fan Operation Fan Operation

If your system does not have a G terminal connection, skip to Heating System Heating System Heating System Heating System Heating System.

and flame icon ( ) to indicate that the Aux. system is operating. 3. Adjust temperature setting to 3° above room temperature. The auxiliary heat system should begin to operate and the display should show STG 1+2. 4. Press to adjust the thermostat below room tempera- ture. The Aux. heating system should stop operating.

1. Turn on power to system. 2. Move fan switch to ON position. The blower should begin to operate. 3. Move fan switch to AUTO position. The blower should stop immediately.

CAUTION !

CAUTION !

Do not allow the compressor to run unless the com- Do not allow the compressor to run unless the com- Do not allow the compressor to run unless the com- Do not allow the compressor to run unless the com- Do not allow the compressor to run unless the com- pressor oil heaters have been operational for 6 hours pressor oil heaters have been operational for 6 hours pressor oil heaters have been operational for 6 hours pressor oil heaters have been operational for 6 hours pressor oil heaters have been operational for 6 hours and the system has not been operational for at least and the system has not been operational for at least and the system has not been operational for at least and the system has not been operational for at least and the system has not been operational for at least 5 minutes. 5 minutes. 5 minutes. 5 minutes. 5 minutes.

To prevent compressor and/or property damage, if To prevent compressor and/or property damage, if To prevent compressor and/or property damage, if To prevent compressor and/or property damage, if To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT the outdoor temperature is below 50°F, DO NOT the outdoor temperature is below 50°F, DO NOT the outdoor temperature is below 50°F, DO NOT the outdoor temperature is below 50°F, DO NOT operate the cooling system. operate the cooling system. operate the cooling system. operate the cooling system. operate the cooling system.

Cooling System Cooling System Cooling System Cooling System Cooling System

Heating System Heating System Heating System Heating System Heating System

1. Press SYSTEM button to select the Snowflake icon Snowflake icon Snowflake icon Snowflake icon Snowflake icon ( ). 2. Press to adjust thermostat setting below room temperature. The blower should come on immediately on high speed, followed by cold air circulation. The display should show STG1. 3. Adjust temperature setting to 3° below room temperature. The second stage cooling should begin to operate and the display should show STG 1+2. 4. Press to adjust the temperature setting above room temperature. The cooling system should stop operating.

1. Press SYSTEM button to select the Flame icon Flame icon Flame icon Flame icon Flame icon ( ). If the auxiliary heating system has a standing pilot, be sure to light it. 2. Press to adjust thermostat setting to 1° above room temperature. The heat pump system should begin to operate. The display should show STG1. However, if the set point temperature display is flashing, the compressor lockout feature is operating (see Configuration menu, item 5). 3. Adjust temperature setting to 3° above room temperature. If your system configuration is set at MS2, HP2 or HP1, the auxiliary heat system should begin to operate and the display should show STG 1+2. 4. Press to adjust the thermostat below room tempera- ture. The heating system should stop operating.

Page 5 of the White Rodgers 1F83-277 user manual — CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU
Page 5 · click to enlarge
Page 5

OPERATION

Before you begin programming your thermostat, you should be familiar with its features and with the display and the location and operation of the thermostat buttons. Your thermostat consists of two parts: the thermostat cover and the base. To remove the cover, pull it straight out from the base. To replace the cover, line up the cover with the base and press until the cover snaps onto the base.

White Rodgers 1F83-277 — OPERATION OPERATION OPERATION OPERATION OPERATION diagram (page 5)
Fig. 2

The Thermostat Buttons and Switches The Thermostat Buttons and Switches The Thermostat Buttons and Switches The Thermostat Buttons and Switches The Thermostat Buttons and Switches

1 Raises temperature setting

2 Lowers temperature setting.

3 FAN switch (ON, AUTO)

4 SYSTEM button (COOL, AUTO, HEAT, EMER, OFF)

The Display The Display The Display The Display The Display

5 Flame icon Flame icon Flame icon Flame icon Flame icon ( ) is displayed when the system is in HEAT mode. Snowflake icon Snowflake icon Snowflake icon Snowflake icon Snowflake icon ( ) is displayed when

the system is in COOL mode. Flame icon Flame icon Flame icon Flame icon Flame icon ( ) and Snowflake icon Snowflake icon Snowflake icon Snowflake icon Snowflake icon ( ) are displayed simultaneously when thermostat is in AUTO mode.

6 Displays BATT when the 2 "AA" batteries are low and should be replaced. Only BATT and LO are displayed when batteries are low with no system power.

Figure 6 – Thermostat display, buttons and switches Figure 6 – Thermostat display, buttons and switches Figure 6 – Thermostat display, buttons and switches Figure 6 – Thermostat display, buttons and switches Figure 6 – Thermostat display, buttons and switches

11 EMER is displayed flashing when the system is in EMER mode.

7 Displays current temperature or LO when batteries are low.

12 Indicates a fault in the heating/cooling system. It does not indicate a fault in the thermostat.

8 Displays currently programmed set temperature (this is blank when SYSTEM is OFF).

13 Display ( ) when limited range is activated.

9 Displays FLTR when the system has run for the programmed filter time period as a reminder to change or clean your filter.

14 Stage1 & 2 Stage1 & 2 Stage1 & 2 Stage1 & 2 Stage1 & 2 indicators: The thermostat shall indicate when the first and second stage is energized except in emergency mode. The icon is STG 1 STG 1 STG 1 STG 1 STG 1 for the first stage energized. The icons for the first and second stage energized are STG1+2 located in the upper right side of the display.

10 Display ( ) when in keypad lockout mode.

CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU

The configuration menu allows you to set certain thermostat operating characteristics to your system or personal require- ments.

2. Fast or Slow Cycle Selection Fast or Slow Cycle Selection Fast or Slow Cycle Selection Fast or Slow Cycle Selection Fast or Slow Cycle Selection – The factory default setting is fast cycle, which cycles 1st stage at approximately 1.2°F and 2nd stage 0.75°F. If you prefer slow cycle, press the temperature key to change to SL. The 1st stage and 2nd stage would be 1.5°F and 1.2°F respectively.

Set SYSTEM button to OFF, then simultaneously press and to enter configuration menu. The display will show the first item in the configuration menu.

3) Select Compressor Lockout CL OFF or ON Select Compressor Lockout CL OFF or ON Select Compressor Lockout CL OFF or ON Select Compressor Lockout CL OFF or ON Select Compressor Lockout CL OFF or ON – Selecting CL ON will cause the thermostat to wait 5 minutes before turning on the compressor if the heating and cooling system loses power. It will also wait 5 minutes minimum between cooling and heating cycles. This is intended to help protect the compressor from short cycling. Some newer compres- sors already have a time delay built in and do not require this feature. Your compressor manufacturer can tell you if the lockout feature is already present in their system. When the thermostat compressor time delay occurs it will flash the setpoint for about five minutes.

The configuration menu table summarizes the configuration options. An explanation of each option follows.

Press SYSTEM to change to the next menu item. To exit the menu and return to the program operation, press RUN. If no keys are pressed within fifteen minutes, the thermostat will revert to normal operation.

1) Single Stage, Multi-stage or Heat Pump System Single Stage, Multi-stage or Heat Pump System Single Stage, Multi-stage or Heat Pump System Single Stage, Multi-stage or Heat Pump System Single Stage, Multi-stage or Heat Pump System Configuration – This control can be configured for Heat Pump or two stage heat/two stage cool multi-stage opera- tion. The display indicates MS 2 MS 2 MS 2 MS 2 MS 2 (default for multi-stage mode) in the display. The Multi-stage configuration can be toggled to SS1, HP2, or HP1 by pressing the Tempera- ture Up ture Up ture Up ture Up ture Up or Temperature Down Temperature Down Temperature Down Temperature Down Temperature Down key. In Multi-stage configu- ration, system button will not have EMERgency mode.

Page 6 of the White Rodgers 1F83-277 user manual — CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU
Page 6 · click to enlarge
Page 6

CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU

Press the System button until OFF is displayed, then press the and simultaneously INSTALLER/CONFIGURATION MENU StepPress Button(s)Displayed (Factory Default)Press or to selectComments 1SystemMS 2SS1, HP2, HP1Selects Single stage, Multi-stage, or Heat Pump (Single stage or 2-stage) System Configuration 2SystemFASLSelects Fast or Slow Cycle Selection 3SystemCL (OFF)CL (ON)Selects Compressor Lockout CL OFF or ON 4SystemCDL (ON)CDL (OFF)Selects Backlight Display 5SystemFA (ON)FA (OFF)Selects Fast Second Stage ON or OFF 6System0 FLTR50-1950 (increments of 50)Selects filter replacement run time 7System0°F (Room Temperature)4 LO to 4 HISelects Temperature Display Adjustment 4 LO to 4 HI 8System°F°CFor °C selection 9SystemLR (90)LR 62 to LR89Selects Limited HEAT range 10SystemLR (45)LR 46 to LR 82Selects Limited COOL range 11SystemCA (OFF)CA (ON)Feature Not Available 12System(OFF)(ON)Selects Keypad Lockout 130001 to 999Selects Keypad lockout combination number Press System to set code 14SystemReturns to the OFF position

4) Select Backlight Display Select Backlight Display Select Backlight Display Select Backlight Display Select Backlight Display – The display backlight improves display contrast in low lighting conditions. When the "C" terminal is powered, selecting backlight CdL ON will keep the light on continuously. Select backlight OFF will keep the light on momentarily after any key is pressed. When the "C" terminal is not powered, the light will be on momentarily after any key is pressed no matter the backlight is selected ON or OFF.

7) Select Temperature Display Adjustment 4 LO to 4 HI Select Temperature Display Adjustment 4 LO to 4 HI Select Temperature Display Adjustment 4 LO to 4 HI Select Temperature Display Adjustment 4 LO to 4 HI Select Temperature Display Adjustment 4 LO to 4 HI – Allows you to adjust the room temperature display up to 4° higher or lower. Your thermostat was accurately calibrated at the factory but you have the option to change the display temperature to match your previous thermostat. The cur- rent or adjusted room temperature will be displayed on the left side of the display.

8. Select F° or C° Readout Select F° or C° Readout Select F° or C° Readout Select F° or C° Readout Select F° or C° Readout – Changes the display readout

to Centigrade or Fahrenheit as required.

5) Select (Fast) Second Stage ON or OFF Select (Fast) Second Stage ON or OFF Select (Fast) Second Stage ON or OFF Select (Fast) Second Stage ON or OFF Select (Fast) Second Stage ON or OFF – In the run mode, if the setpoint temperature is manually raised by 3°F (2°C) or more above the actual temperature with the , and the fast second stage feature is enabled, FA ON, the second stage will energize immediately. With FA OFF, second stage will not energize until the setpoint temperature is 1°F or more above actual temperature for more than ten min- utes.

9. Limited Heat Range Limited Heat Range Limited Heat Range Limited Heat Range Limited Heat Range – This feature provides a maximum

setpoint temperature for heat. The default setting is 90°F. It can be changed between 62°F and 89°F by pressing the temperature up temperature up temperature up temperature up temperature up or temperature down temperature down temperature down temperature down temperature down key.

10. Limited Cool Range Limited Cool Range Limited Cool Range Limited Cool Range Limited Cool Range – This feature provides a minimum setpoint temperature for cool. The default setting is 45°F. It can be changed between 46°F and 82°F by pressing the temperature up or temperature down key.

6) Select filter replacement run time Select filter replacement run time Select filter replacement run time Select filter replacement run time Select filter replacement run time – The thermostat will display FLTR after a set time of operation. This is a remind- er to change or clean your air filter. This time can be set from 0 to 1950 hours in 50 hour increments. A selection of 000 A selection of 000 A selection of 000 A selection of 000 A selection of 000 will cancel this feature will cancel this feature will cancel this feature will cancel this feature will cancel this feature. When FLTR is displayed, you can clear it by pressing HOLD and RUN at the same time. This resets the timer and starts counting the hours until the next filter change. Contact your system manufacturer for a specific replacement/maintenance interval.

11. This feature not available This feature not available This feature not available This feature not available This feature not available.
Page 7 of the White Rodgers 1F83-277 user manual — OPERATION OPERATION OPERATION OPERATION OPERATION
Page 7 · click to enlarge
Page 7

CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU CONFIGURATION MENU

12 & 13) Keypad Lockout Keypad Lockout Keypad Lockout Keypad Lockout Keypad Lockout – This menu selection will display lock icon. The and are used to toggle the function and display the lock icon and OFF (keypad not locked out, default) indicating in the time digits to the lock icon and ON (keypad locked out). When the keypad lockout function is enabled (ON), and the SYSTEM key is pressed again, the display will indicate the number 0 (default, still disabled) in the time digits. The and are used to set the combina- tion number from 0 to 999. "0" will not be a valid combination. If a combination of 0 is selected and the system key is pressed the menu will be exited and keypad lockout will not be evoked. If 1 to 999 1 to 999 1 to 999 1 to 999 1 to 999 is selected and the SYSTEM key is pressed again, the combination is locked into non-volatile memory and the menu is exited. The lock icon (to designate keypad locked with a valid combination) will display when the menu is exited. The system key will operate for 10 seconds after the menu mode is exited to allow the user to change the mode from OFF to the desired system mode.

While the keypad is locked out, a simultaneous press of the temperature and will enter the menu item from any mode instead of only OFF mode OFF mode OFF mode OFF mode OFF mode. When the menu is entered with the keypad lockout feature enabled, the first menu item displayed is the combination code 0. The or keys are used to set the combination unlock number from 0 to 999. If the unlock number matches exactly with the combination lock number stored in memory when the SYSTEM key is pressed, the keypad is unlocked and the lock icon is removed. If the unlock number does not match when the SYSTEM key is pressed, menu is exited and the keypad remains disabled. To reset the combination code and unlock the keypad if the code is forgotten, see troubleshooting section.

SPECIFICATIONS

ELECTRICAL DATA ELECTRICAL DATA ELECTRICAL DATA ELECTRICAL DATA ELECTRICAL DATA

THERMAL DATA THERMAL DATA THERMAL DATA THERMAL DATA THERMAL DATA

Electrical Rating Electrical Rating Electrical Rating Electrical Rating Electrical Rating:

Setpoint Temperature Range Setpoint Temperature Range Setpoint Temperature Range Setpoint Temperature Range Setpoint Temperature Range:

20 to 30 VAC 50/60 Hz or DC 0.05 to 1.5 Amps (Load per terminal) 2.5 Amps Maximum Total Load (All terminals combined)

45°F to 90°F (7°C to 32°C) Operating Ambient Temperature Range Operating Ambient Temperature Range Operating Ambient Temperature Range Operating Ambient Temperature Range Operating Ambient Temperature Range:

32°F to 105°F Operating Humidity Range Operating Humidity Range Operating Humidity Range Operating Humidity Range Operating Humidity Range:

0 to 90% RH (non-condensing) Shipping Temperature Range Shipping Temperature Range Shipping Temperature Range Shipping Temperature Range Shipping Temperature Range:

OPERATION

The system "mode" is selected by pressing the SYSTEM button. Icons on the bottom right corner of the display will indicate the mode: COOL ( ), AUTO ( ), HEAT ( ), EMER, or OFF. In any mode except OFF, the setpoint temperature will be shown on the right side of the display. In OFF, this area will be blank. The current temperature will be displayed on the left side of the display.

Second Stage Time Delay Second Stage Time Delay Second Stage Time Delay Second Stage Time Delay Second Stage Time Delay

Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force the thermostat to bring the second stage on quickly. There is a time delay from 0-30 minutes depending on the performance of the first stage of the system.

To operate properly in the AUTO mode, the heat setpoint temperature cannot be the same as or higher than the cool setpoint temperature. The heat setpoint must be at least 1° lower than the cool setpoint.

EXAMPLE: For the last 2 hours the thermostat is set on 70° and the room temperature is 70° with the equipment using only the first stage of heat. Since the equipment is keeping the tempera- ture within 1 degree of setpoint, the thermostat will delay second stage for a longer time if you manually raise the temperature or if the room temperature quickly changes. Once the second stage comes on, it will come on sooner the next time there is a difference between the setpoint and the room temperature. The net effect of the staging program is that when the first stage is capable of making temperature the second stage will delay longer. When the thermostat calculates that first stage cannot make temperature in a reasonable time, the second stage will come on sooner. This built in function automatically optimizes the use of additional stages of heat or cool.

Automatic System Changeover Automatic System Changeover Automatic System Changeover Automatic System Changeover Automatic System Changeover

When the thermostat is in the AUTO mode, both the Flame and Snowflake icons are displayed. The thermostat will call for heat or cool depending on the room temperature. The setpoint temperature displayed will be that of the last mode called. If the last system cycle was heat, the HEAT setpoint will be displayed. If the room temperature raises above the HEAT setpoint and the COOL setpoint and a call for cool is required, the temperature displayed will change to be the COOL setpoint.

-40°F to 150°F

Page 8 of the White Rodgers 1F83-277 user manual — TROUBLESHOOTING TROUBLESHOOTING TROUBLESHOOTING TROUBLESHOOTING TROUBLESHOOTING
Page 8 · click to enlarge
Page 8

TROUBLESHOOTING

Reset Operation Reset Operation Reset Operation Reset Operation Reset Operation If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermostat by removing the wires from terminals R and C and removing batteries for 2 minutes. After resetting the thermo- stat, replace the wires and batteries. If the thermostat has been reset and still does not function correctly contact your heating/cooling service person or place of purchase.

Symptom

Possible Cause Possible Cause Possible Cause Possible Cause Possible Cause

Corrective Action Corrective Action Corrective Action Corrective Action Corrective Action

No Heat/No Cool/No Fan (common problems)1.Blown fuse or tripped circuit breaker. 2.Furnace power switch to OFF. 3.Furnace blower compartment door or panel loose or not properly installed.Replace fuse or reset breaker. Turn switch to ON. Replace door panel in proper position to engage safety interlock or door switch. No Heat1.Pilot light not lit. 2.System Switch not set to HEAT. 3.Loose connection to thermostat or system. 4.Furnace Lock-Out Condition. Heat may also be intermittent. 5.Heating system requires service or thermostat requires replacement.Re-light pilot. Set System Switch to HEAT and raise setpoint above room temperature. Verify thermostat and system wires are securely attached. Many furnaces have safety devices that shut down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local service person for assistance. Diagnostic: Set System Switch to HEAT and raise the setpoint above room temperature. Within a few seconds the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating is operating correctly. No Cool1.System Switch not set to COOL. 2.Loose connection to thermostat or system. 3.Cooling system requires service or thermostat requires replacement.Set System Switch to COOL and lower setpoint below room temperature. Verify thermostat and system wires are securely attached. Same procedure as diagnostic for No Heat condition except set the thermostat to COOL and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling. Heat, Cool or Fan Runs Constantly1.Possible short in wiring. 2.Possible short in thermostat. 3.Possible short in heat/cool/fan system. 4.Fan Switch set to Fan On.Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal screws. Try resetting the thermostat as described above. If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat/ Cool system for correct operation. If the system operates correctly, replace the thermostat. Furnace (Air Conditioner) Cycles Too Fast or Too Slow (narrow or wide temperature swing)1.The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate.Digital thermostats normally provide precise temperature control and may cycle faster than some older mechanical models. A faster cycle rate means the unit turns on and off more frequently but runs for a shorter time so there is no increase in energy use. If you would like to increase the cycle time, choose SL for slow cycle in the menu, step 4. If an acceptable cycle rate is not achieved as received or by choosing slow cycle, contact a local service person for additional suggestions.
Page 9 of the White Rodgers 1F83-277 user manual — TROUBLESHOOTING TROUBLESHOOTING TROUBLESHOOTING TROUBLESHOOTING TROUBLESHOOTING
Page 9 · click to enlarge
Page 9

TROUBLESHOOTING

Symptom

Possible Cause Possible Cause Possible Cause Possible Cause Possible Cause

Corrective Action Corrective Action Corrective Action Corrective Action Corrective Action

Thermostat Setting & Thermostat Thermometer Disagree1.Thermostat thermometer setting requires adjustment.The thermometer can be adjusted +/- 3 degrees. See Temperature Display Adjustment in the Configuration Menu section. Blank Display and/or Keypad Not Responding1.Voltage spike or static discharge.Use the Reset Operation at top of previous page. Heat Setpoint will not Respond to the Temperature Up Key1.The desired setpoint conflicts with the setpoint of the COOL mode.Change system mode to COOL. Raise the Cool setpoint. Return to HEAT mode and set desired temperature. Cool Setpoint will not Respond to the Temperature Down Key1.The desired setpoint conflicts with the setpoint of the HEAT mode.Change system mode to HEAT. Lower the Heat setpoint. Return to COOL mode and set desired temperature. Forgot Keypad Lockout CodeCAUTION: This resets the thermostat to factory default settings of the configuration menu. After performing this reset, the thermostat will require configuration again. Be sure that you know the required configuration settings before resetting. With the thermostat in any mode, press and at the same time to enter the configuration menu at the point where the lockout code is to be entered. Press and and SYSTEM button at the same time to reset the lockout code, unlock the keypad and reset all configuration menu settings. Why won't my 2nd or 3rd stage come on?Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force the thermostat to bring the second stage on quickly. There is a time delay from 0-30 minutes depending on the performance of the first stage of the system.
Page 10 of the White Rodgers 1F83-277 user manual — TROUBLESHOOTING TROUBLESHOOTING TROUBLESHOOTING TROUBLESHOOTING TROUBLESHOOTING
Page 10 · click to enlarge
Page 10

The Emerson logo is a trademark and a service mark of Emerson Electric Co.

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the White Rodgers 1F83-277

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the White Rodgers 1F83-277

Be the first to ask — other owners or our team will answer.

Original document

White Rodgers 1F83-277 manual PDF

10 pages·176 KB·Thermostat·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…